VESDA-E VEP
VESDA-E VEP
VESDA-E VEU Specifications

VESDA-E VEU

Detector Specifications - VEU A00 & A10

Supply Voltage:

18 to 30VDC

 

Power Consumption @ 24VDC: (Vesda E VEU A00)

Aspirator @ 1: Quiescent 7W - In Alarm 7.8W

Aspirator @ 5: Quiescent 8.8W - In Alarm 9.6W

Aspirator @ 10: Quiescent 14.7W - In Alarm 15.5W

 

Dimensions (WHD):

350 mm x 225 mm x 135 mm (13.8 in x 8.9 in x 5.3 in)

 

Weight:

Vesda-E VEU A00 - 4.800 kg (10 lbs 9 oz)

Vesda-E VEU A10 - 4.835 kg (10 lbs 10 oz)

 

Operating conditions:

Ambient: 0°C to 39°C (32°F to 102°F)

Sampled Air: -20°C to 60°C (-4°F to 140°F)

Tested to: -20°C to 55°C (-4°F to 131°F)

Humidity: 10% to 95% RH, non-condensing

 

Air Sampling Pipe Network:

Maximum area of Coverage: 2,000 m2 (21,500 sq.ft)

Minimum airflow per pipe: 15 l/m

 

Maximum pipe lengths:

Total Pipe Length (with branches): 800 m (2624 ft)

Maximum length per pipe, when using four straight pipes: 100 m (328 ft)

 

Computer design tool:

Xtralis ASPIRE-ETM For Vesda-E VEU, VEA and VEP

 

Pipe:

Inlet: External diameter 25 mm or 1.05 in (3/4 in IPS)

Exhaust: External diameter 25mm or 1.05 in (3/4 in IPS) via adaptor

 

Relays:

7 programmable relays (latch or non-latch states) Contacts rated 2 A @ 30 VDC (Resistive)

 

IP rating:

IP40

 

Cable access:

4 x 26 mm (1.02 in) cable entries

 

Cable termination:

Screw Terminal blocks 0.2–2.5 sq mm (30–12 AWG)

 

Dynamic Range:

0.0002%/m (0.00006% obs/ft) to 20% obs/m (6.25% obs/ft)

 

Sensitivity Range:

0.001% - 20.0% obs/m (0.0003 to 6.25% obs/ft)

 

Threshold setting range:

Alert: 0.001%-2.0% obs/m (0.0003%-0.625% obs/ft)

Action: 0.001%-2.0% obs/m (0.0003%-0.625% obs/ft)

Fire1: 0.001%-2.0% obs/m (0.0003%-0.625% obs/ft)

Fire2: 0.001%-20.0% obs/m (0.0003%-6.25% obs/ft)

 

Software features:

Event log: Up to 20,000 events stored in FIFO format, smoke level, user actions, alarms and faults with time and date stamp.

AutoLearn: Min 15 minutes, Max 15 days. Recommended minimum 1 day. While AutoLearn is in progress, thresholds are NOT changed from pre-set values.

 

VESDA Wholesale

Stay updated about this product.

Visit us on Facebook Visit us on Twitter Visit us on Google+ Visit us on LinkedIn
* indicates required